Stream SCADA can communicate to PLC and other devices that support Modbus TCP communication. In this case, Stream SCADA acts as the Modbus TCP Client and the PLC is the Modbus TCP Server.


From Stream Explorer, select Data Sources and click on the Add button.


Main Tab:



  • Name: Unique name for the data source.
  • Description: Optional information about the data source.
  • Data Source Type: Selecting Modbus TCP means that Stream SCADA is Modbus TCP client that will initiate communications with a Modbus TCP Server (e.g. a PLC).
  • Cycle: This is the scan rate for this data source.


  • IP address: Type here the IP address of the Modbus Server device (e.g. the PLC).

Note: If you have more than one IP address (redundant), type them separated with semi column. Example: 10.10.10.1;10.10.10.2


  • Port No.: Device port number. The default for Modbus is 502.
  • Slave ID: Each Modbus device (Server or Slave) in a network is assigned a unique unit address from 1 to 247.
  • Timeout: Configures operation or socket time-out
  • Retry: Configures the automatic retry setting. A value of 0 disables any automatic retries.


  • Big Indian Integers: This option is required to read data correctly from a big-indian device.
  • Swapped Floats: This option is required to read data correctly in some cases (Words order need to be swapped).


  • Status Tag: Select or type a Boolean tag name that will become True only when if the device comm status is healthy.




Ranges Tab:


Here we define the exact addresses ranges that need to be scanned. The address of any defined tag should fall within one of the defined ranges.


Currently, There are three types of Modbus actions (meaning 3 types of scans) that Stream SCADA can perform:


1. Read Coils

Performs Modbus Function Code 1 (01 hex). Define the start coil number in Start and define how many coils to be read in this scan in Count. Up to 2000 coils can be read in one scan.


2. Read Holding Registers

Performs Modbus Function Code 3 (03 hex) for integer data types (16-bit). Define the start holding register number in Start and define how many holding registers to be read in this scan in Count. Up to 125 coils can be read in one scan.


2. Read Holding Floats

Performs Modbus Function Code 3 (03 hex) for floating data types (32-bit). Define the start holding register number in Start and define how many floats to be read in this scan in Count. Up to 62 floats can be read in one scan.



The above example instructs Stream SCADA to perform the following during runtime:


  1. Read Coils from 1 to 500.
  2. Read Holding Registers from 1 to 100.
  3. Read Holding Registers from 100 to 150.
  4. Read Floats from 200 to 220.


Note: You can copy the entire table of ranges from Excel. Simply by Ctrl+C and then Ctrl+V.